Energy Power Meter
Product: EPM-35
- Network Selection: 1Ø-2W, 3Ø-3W, 3Ø-4W
- 20 to 300V AC (L-N), 35 to 520V AC (L-L)
- RS-485 Modbus Communications
- Supply voltage: 100 to 270V AC/DC
| PARAMETER SPECIFICATION | |
| Input Signal | 3Ø 3 Wire / 3Ø 4Wire / 1Ø 2Wire |
| CT Primary | up to 9999A (Programmable) |
| CT Secondary | 5 Amp/1 Amp selectable |
| PT Primary | 100V to 520kV (Programmable) |
| PT Secondary | 100V to 520V (L-L) (Programmable) |
| Sys. PF & Per Phase | 0.100 - 1.000 |
| Frequency (Hz) | 45.00 - 60.00 Hz |
| POWER | |
| kW Total | 0.000 - 9999 MW |
| kVA Total | 0.000 - 9999 MVA |
| kVAr Total | 0.000 - 9999 MVAr |
| Energy | |
| kWh Import | 000.000 - 99999999 MWh |
| kWh Export | 000.000 - 99999999 MWh |
| kVAh Total | 000.000 - 99999999 MVAh |
| kVArh Import | 000.000 - 99999999 MVArh |
| kVArh Export | 000.000 - 99999999 MVArh |
| DISPLAY & KEY | |
| Display | LCD |
| Key | SET, INC, DEC |
| DIMENSION | |
| Size (mm) | 90 (H) x 35 (W) x 72 (D) mm |
| AUXILIARY SUPPLY | |
| Supply voltage | 100 to 270V AC/DC |
| ACCURACY | |
| Class 0.5 (Standard) | |
| ENVIRONMENT CONDITION | |
| Operating Temp. | 0°C to 55°C |
| Relative Humidity | Upto 95% RH |
| (non-condensing) | |
- Electrical Control Panel
- Power Distribution
- Instrumentation Panel
- Transformer training
Related Products
Reach Us
Reach out to us to receive more information, technical support, assistance, and more
Contact UsContact Sales
For any assistance or queries, please reach out to our support team. To get prompt solutions and address your concerns
Contact an expertVisit our IIOT Site
Explore our IIOT site for solutions that connect machines, data, and people to optimize industrial processes and drive business growth.
Explore now